
Design Considerations – Identification Report (DC/06/18/3p)
The use of damp courses and trays in cavity construction
and the necessity to envelope all placements within mortar.
This identification report concerns the use of
conventional roll dpc and preformed dpc trays (cavity trays) when used within
cavity wall construction. The observations and recommendations identified refer
to use at all levels of construction appertaining to the building envelope,
from ground level to plate level. Unless otherwise stated all are applicable to
both skins of a conventional cavity wall where such skins are constructed of
masonry.
In the United Kingdom construction work must be
executed in accordance with the Building Regulations. The Building Regulation
publications include a list of relevant British Standards.
BS 5628-3:2005 is the Code of Practice for the Use
of Masonry and provides information and guidance regarding how dpc and trays
are to be incorporated:
‘All dpc and cavity trays
must be laid on a smooth bed of fresh mortar’. ((BS 5628 extract)
This
is not a new requirement but one that has applied for decades. The two leading
providers of UK construction and standards warranties stipulate the following:
The structural design must be in accordance with
Building Regulations and BS 5628 and additionally the need is emphasised in
some locations to use only a dpc that can achieve a good key with the mortar.
(NHBC Standards 6.1)
The NHBC Standards includes the following requirements
regarding use of dpc’s:
Dpc’s should be laid on a surface, free from
projections that could puncture or adversely affect the dpc material.
Dpc’s should be fully bedded on fresh mortar.
To ensure structural robustness and weather
resistance, masonry units should be laid on a full bed of mortar. (NHBC Standards extracts)
Zurich Insurances enforces the same requirement, but
in one sentence:
‘A dpc should be laid between a smooth mortar bed
and lapped at junctions’.
(Zurich Insurances – superstructure extract)
Additionally Zurich Insurances refer to observance
of BS 8000:4.
Therefore to construct in accordance with the
Building Regulations, to construct in accordance with the relevant British
Standards, and to comply with the requirements of both the NHBC and Zurich
Insurances, no dpc or tray must be laid dry-bedded.
If
a masonry cavity wall is to be deemed compliant, all dpc’s and trays
incorporated therein must be bedded on mortar and the subsequent masonry laid
must be bedded on mortar also.
Consequences
of Dry Bedding
Dry bedding means elements of the building envelope
are not structurally enveloped. This can adversely affect the performance and
the life of the structure.
Inside Skin
Where dry bedding occurs within the inner skin (most
commonly at ground floor level) any absence of mortar may subsequently
influence the airtightness of the structure.
Where the dpc is built into the inside skin at a higher level (for
instance to provide support for a dpc that rises and crosses within the cavity),
the absence of mortar similarly does not promote structural or airtightness
qualities. The thermal behaviour qualities anticipated of an inner skin can be
reduced where there is intermittent bonding or an absence of bonding material
that would normally be present to provide a continuance of structural adhesion.
(Recommended reading BRE Thermal Insulation:
Avoiding Risks)
Exterior Skin
Where dry bedding occurs in the
external skin, the structural adhesion of the weathering wall is discontinuous.
This gives rise to subsequent behaviour witnessed during severe rain
conditions:
Dry-bedded features are
liable to capillary action once saturation point of the masonry/mortar in the
immediate vicinity of the dry bedding is reached. Because a dpc must extend
through the thickness of a masonry skin, the commencing point for such
behaviour is on the exterior masonry face. The movement of liquid in the interstices of a
porous material (as a result of surface tension) promotes the phenomenon
responsible for dry materials sucking moisture beyond or above normal water
permeating depths. Water ingress is the result of a combination of
adhesion and cohesion of intermolecular forces between the liquid and a substance
stronger than the cohesive intermolecular forces inside the
liquid. Hence the necessity to lay all dpc’s and trays
within a bed of mortar so envelopment is achieved plus the accompanying
structural bonding.
Dry bedding can also
promote spalling. In a bed joint lacking mortar, any retained or pooling water
is susceptible to freezing when a wet
wall is exposed to a temeperature drop. The concentration of liquid along a
bedding joint is neither structurally or aesthetically beneficial.
If this occurs at higher
level such as within a parapet or running coping, there is the added exposure
of thermal and moisture temperature swings manifesting in parapet ratcheting.
Hence at coping level there is the added requirement for a minimum mass (25kg per metre run) to
promote stability. Where dry
bedding occurs behind an external render coat, the structure is susceptible to
water rentention and tell-tale signs of normally manifest within a few years.
The render coat will eventually crack and delaminate. Such risks are present if
dpc and trays are dry bedded – hence the need to observe the regulations,
requirements and reccommendations of the authoratitive bodies.
Manufacturers Viewpoint
All dpc manufacturers
contacted confirmed the instructions for use of their material stipulated
bedding within mortar. This was in printed form and in many instances available
on the internet also.
All cavity tray
manufacturers contacted confirmed identical instructions. This was in printed
form and in many instances available on the internet also. Some manufactuers
pointed out the instruction ‘Do not dry bed’ is additionally moulded into their
product so it is facing the installer every time.
Frost / Sulphate Attack of
the Outer Leaf
The frost resistance of masonry
is diminished if the masonry skin permits retention of water within voids,
intermittent joins or if pooling exists within a structure and is not readily
evacuated. The degree of exposure to wind driven rain combined with the
frequency of freeze and thaw cycles are the main factors affecting frost
attack. Dry bedding of a dpc or tray increases the risk because water is both
retained and channelled by capillary action.
The length of time the
masonry is wet, and the interaction of soluble salts used in masonry units and
cement used for the mortar directly influences sulphate damage of mortar. If
water retention is present because it cannot readily evacuate, the exposure to
risk is increased. Dry bedding of a dpc or tray increases the risk because water
is both retained and channelled by capillary action.
Conclusion
Failure to bed dpc’s and
trays in mortar introduces deficiencies and as a consequence the structure is
susceptible to numerous deficiencies in the immediate and long term, some of
which will affect the ability of the construction to provide the requisite
protection against damp and thermal elements, as demanded by the Building
Regulations applicable in England, Scotland and Wales. If a masonry wall is to be
deemed compliant, all dpc’s and trays incorporated therein must be bedded on
mortar and the subsequent masonry laid must also be bedded on mortar.
Footnote
Perhaps the situation is best summed up by a site
agent given the task of ‘trouble shooting’ various properties in which the
dpc’s had been dry bedded. The properties were suffering water ingress at
various high level intersections because of the omission.
‘If a glazier came on to my site to bed and putty
the glass into the window frames but used no putty at all and put the glass in
dry, he would hardly expect the rain not to come in – would he? ….. As for
cavity construction, it’s in the requirements and it’s in the instructions, (to bed dpc and trays in
mortar) so there’s no excuse’.
References:
James
Long Design (background information)
NHBC
Technical Manual
Robust
Details
Zurich
Insurances
British
Standard 5628-3:2005
British
Standard 8000:4.
Cavity
Trays Ltd Technical Manual 17.
BRE:
Thermal Insulation: Avoiding Risks.

|
The Cavity Tray Standards
website provides information, news, guidelines and articles on cavity trays,
flashings and damp courses.
A wide range of options are
available to the specifier and contractor, and the objective of the website
is to provide guidance to help in the selection of the most appropriate
specification for your project.
www.cavitytraystandards.co.uk
|
|
P.O. BOX 235
West Park Sorting Office
PLYMOUTH
Devon
PL5 3WA
December 2006.
|